Electical & Physical Data

SPECIFICATIONS CONCEALED FANCOIL UNIT MODEL " FCC "

FANCOIL UNITMODEL

FCC 400

FCC 600

FCC 800

FCC 1200

FCC 1600

FCC 2000

FCC 2400

Cooling Capacity

BTU/Hr.

10000 - 13000

16500 - 21000

26300 - 30200

34200 - 40900

45500 - 50000

57300

63900

Kcal/Hr.

2520 - 3280

4160 - 5392

6620 - 7610

8810 - 10330

10330 - 12600

14490

16100

Air flow Rate

CFM.

300 - 450

450 - 650

700 - 1100

1100 - 1300

1400 - 1600

1800 - 2000

2000 - 2200

Power Supply

Ph/V/Hz

220-240/1/50

Fan Motor

Hp. x Qty.

1 / 20

1 / 15

1 / 10

1 / 15 x 2

1 / 10 x 2

RPM.

400 - 1100             3 Speeds

FLA.

0.3

0.4

0.5

0.8

1.0

Air Filter

Material

Washable, Honey - Comb Net Synthetic Type

Evaporator Coil

Rows/fin
per inch

3 / 12

4 / 12

Tube Size
MM (inch)

9.52 (3 / 8)

Control

Wire /Wireless Remote Control

Connection OD.mm (in)

Suction

12.70 (1/2 )

15.90 (5/8)

19.05 (3/4)

22.22 (7/8)

Liquid

9.52 (3/8)

12.70 (1/2 )

Drain

12.70 (1/2 )

Dimension

WxHxD (mm.)

1143x667x234

1372x667x234

1715x667x234

2058x667x234

: FCC Model

A

845

985

1328

1670

B

667

806

1155

1492

Note :
@ Rating BTUH at 45F Refrigerant temp 80F (26.7C) DB., 67F (19.4C) W.B. entering air to indoor coil.

-    c l i c k    h e r e    f o r    m o r e    i n f o r m a t i o n    -


- back to top -

 
A.R.C. Engineering Co., Ltd.
389/114 Moo 6, Sukhumvit Road
Naklua,  Banglamung,
Chonburi, Thailand 20150

Tel: 038 716867-8
Fax: 038 716869
Mobile: 01 8229968
Email: arccoltd@loxinfo.co.th

Copyright © 2002 A.R.C. Engineering Co., Ltd. All  Rights Reserved.